(2) |
International Fire Code
(IFC), 2006 Edition Modifications:
(a) |
Modifications to Chapter 1:
1. |
Delete section 101.1 in its entirety an substitute in its place the following:
"101.1 Title.The International
Fire Code, 2006 edition, published by the International Code Council,
when used in conjunction with this Chapter, shall be known as a Georgia
State Minimum Fire Prevention Code, hereafter referred to as 'this
code'."
|
2. |
Delete
section 101.3 in its entirety and substitute in its place the following:
"101.3 Purpose and intent. The primary
purpose of this Code, as adopted, is to provide, along with
other adopted codes and standards, for the reasonable minimum protection of
life and property from the hazards created by fire, smoke, explosion, or panic
created from a fear of fire or smoke. It is intended that the purposes of this
Code be accomplished by:
(1) Coordinating application and enforcement of its
provisions with those of other applicable laws, rules, regulations, codes, and
standards; and,
(2) By coordinating the application of its provisions, where
possible, with educational programs or efforts designed to bring about changes
in high risk attitudes and behaviors that are the root causes of most fire
related problems in Georgia; and
(3) By encouraging or requiring informational and awareness
programs designed to make the citizens of Georgia aware of their
responsibilities for compliance with this Code as well as the
other Rules and Regulations of the Safety Fire Commissioner. The intent of this
Code is to establish the minimum requirements, consistent with
nationally recognized good practice, for providing a reasonable level of life
safety and property protection from the hazards of fire, explosion, or
dangerous conditions in new and existing buildings, structures, and premises
and to provide safety to fire fighters and emergency responders during
emergency operations."
|
3. |
Add an exception to section 102.1 to read as follows:
"Exception: This Code does not apply to one-
and two-family dwellings or one- and two-family row houses (townhouses)
separated by a 2-hour fire wall containing not more than three dwelling units
per structure."
|
4. |
Add an
exception to section 102.2 to read as follows:
"Exception: This Code does not apply to one-
and two-family dwellings or one- and two-family row houses (townhouses)
separated by a 2-hour fire wall containing not more than three dwelling units
per structure."
|
5. |
Delete
section 102.3 in its entirety and substitute in its place the following:
"102.3 Change of use or occupancy. No change
shall be made in use or occupancy of any building or structure that would place
the structure in a different division of the same group or occupancy or in a
different group of occupancies, unless such structure is made to comply with
the requirements of this Code, as may be applicable, as well
as those of the International Building Code (IBC), as adopted
by the Department of Community Affairs. Pursuant to O.C.G.A.
25-2-14, due to a change of use or
occupancy of a building or structure the building or structure shall be treated
as a proposed (new) building. (Refer to 103.3 of this Code
regarding the requirements applicable to proposed (new) buildings and
structures.)"
|
6. |
Delete
section 102.4 in its entirety and substitute in its place the following:
"102.4 Application of the building code. The
design and construction of proposed (new) buildings and structures shall comply
with the International Building Code (IBC), as modified and
adopted by the Georgia Department of Community Affairs. Repairs, alterations,
additions, changes in use of occupancy classification, or changes in buildings
or structures required by provisions of the IFC, and which are
within the scope of the IBC, shall be made in accordance with
the IBC, for purposes of this Chapter..
|
7. |
Delete section 102.5 in its entirety and
insert in its place the following:
"102.5 Historic Buildings. Refer to 102.1 and
102.2 regarding the application of this Code to existing
buildings. Except to the extent required by applicable laws of Georgia, the
provisions of this Code are not mandatory for buildings or
structures identified and classified by the state, or as appropriate, a local
jurisdiction, as historic buildings when such buildings or structures are
judged by the fire code official to be safe and in the public interest of
health, safety and welfare. When evaluating the safety of historic buildings
the fire official should consult O.C.G.A. Title 8, Chapter 2 Article 3
entitled, 'Uniform Act for the Application of Building and Fire Related Codes
to Existing Buildings,' and the provisions of O.C.G.A. Sections
25-2-13(b)(3)&
25-2-13(b)(4),
and NFPA Standard 914, Code for Fire Protection of Historic Structures,
as adopted by this Chapter as a recommended
practice."
|
8. |
Delete section
102.6 in its entirety and substitute in its place the following:
"102.6 Referenced codes and standards. Where
the provisions of this Code or the standards referenced
thereby and in Chapter 45 of this Code do not apply to the
specific subjects, situations or conditions encountered that involve risks to
life and property from the hazards of fire, panic from fear of fire or smoke,
or related hazards, compliance with the applicable chapters of the Rules and
Regulations of the Safety Fire Commissioner shall be evidence of compliance
with this Code."
|
9. |
Add a new section 102.10 to read as
follows:
"102.10 Coordination of provisions. This
Code shall apply to all buildings, structures and facilities
as provided in subsections 102.1 and 102.2, and shall be utilized in
conjunction with codes and standards specified inTable
102.10entitled, "CODES REFERENCE GUIDE."
Table 102.10: CODES REFERENCE
GUIDE
|
Area
|
Primary
|
Supplement
|
Occupancy Classification
|
LSC
|
IBC
|
Building Construction Types
|
Including allowable height,
|
allowable building areas, and the
|
IBC
|
LSC
|
requirements for sprinkler protection
|
related to minimum building
|
construction types.
|
Means of Egress
|
LSC
|
NONE
|
Standpipes
|
IBC
|
IFC
|
Interior Finish
|
LSC
|
NONE
|
HVAC Systems
|
IMC
|
NONE
|
Vertical Openings
|
LSC
|
NONE
|
Sprinkler Systems minimum construction
standard
|
LSC
|
NONE
|
Fire Alarm Systems
|
LSC
|
NONE
|
Smoke Alarms and Smoke Detection Systems
|
State
Statute and LSC
|
NONE
|
Portable Fire Extinguishers
|
IFC
|
NONE
|
Cooking Equipment
|
LSC and NFPA 96
|
NONE
|
Fuel Fired Appliances
|
IFGC
|
NFPA 54
|
Liquid Petroleum Gas
|
NFPA 58 NFPA 52
|
NFPA 54 or IFGC
|
Compressed Natural Gas
|
NONE
|
|
10. |
Delete section 103 and all sections there under in their entirety and
substitute in its place the following:
"SECTION 103
GENERAL PROVISIONS FOR EXISTING AND PROPOSED (NEW)
BUILDINGS.
"103.1 General Provisions. The administration,
enforcement and penalty provisions of O.C.G.A. Title 25, Chapter 2, and the
administrative provisions of the various chapters of the Rules and Regulations
of the Safety Fire Commissioner shall apply to and regulate the application and
enforcement of this Code by the Safety Fire Division of the
Office of the Safety Fire Commissioner.
NOTE: Nothing herein shall be construed as prohibiting any
local jurisdiction from adopting the deleted portions of Chapter 1 of this
Code for local purposes, provided, however, local amendments
shall not be less restrictive than this Code, and other codes
and standards as adopted by the various chapters of the Rules and Regulations
of the Safety Fire Commissioner.
103.1.1 The provisions of O.C.G.A. Title 25,
Chapter 2, and other applicable state laws, and the applicable provisions of
various chapters of the Rules and Regulations of the Safety Fire Commissioner
regarding the requirements for certificates, licenses, permits, plan reviews,
inspections, approvals, fees, etc. shall apply and are in addition to any
requirements of local jurisdictions. Local authorities having jurisdiction need
to be consulted to determine if rules and regulations of the local jurisdiction
regarding the requirements for local certificates, licenses, permits, plan
reviews, inspections, approvals, fees, etc. also apply.
103.1.1.1 The administrative, operational, and
maintenance provisions of this Code, with regard to the Safety
Fire Division of the Office of the Georgia Safety Fire Commissioner, shall be
limited to the scope and intents and purposes of the Official Code of Georgia
Annotated (O.C.G.A.) Title 25, Chapter 2, and the Commissioner's Rules and
Regulations.
103.1.1.1.1 Pursuant to O.C.G.A.
25-2-13(d), every
person who owns or controls the use of any building, part of a building, or
structure described in O.C.G.A
25-2-13(b)(1),
which because of floor area, height, location, use or intended use as a
gathering place for large groups, or use or intended use by or for the aged,
the ill, the incompetent, or the imprisoned, constitutes a special hazard to
property or to the life and safety on account of fire or panic from fear of
fire, must so construct, equip, maintain, and use such building or structure as
to afford every reasonable and practical precaution and protection against
injury from such hazards. No person who owns or controls the use or occupancy
of such a building or structure shall permit the use of the premises so
controlled for any such specially hazardous use unless he has provide d such
precautions against damage to property or injury to persons by these hazards as
are found and determined by the Commissioner in the manner described in
O.C.G.A. 25-2-13(d) to be
reasonable and practical.
103.2Existing buildings. Every
building and structure existing as of April 1, 1968, which building or
structure is listed in paragraph (1) of subsection (b) of O.C.G.A
25-2-13shall comply with the
minimum fire safety standards in the Rules and Regulations of the Safety Fire
Commissioner promulgated pursuant to O.C.G.A.
25-2which were in effect at the
time such building or structure was constructed.
Exception 1: Any nonconformance noted under the electrical
standards adopted at the time such building or structure was constructed shall
be corrected in accordance with the current electrical standards adopted
pursuant to O.C.G.A.
25-2.
Exception 2: A less restrictive provision contained in any
subsequently adopted minimum fire safety standard pursuant to O.C.G.A.
25-2, may be applied to any
existing building or structure.
103.2.1 Existing buildings to be deemed a proposed
building. For the purposes of O.C.G.A.
25-2-14(b), any
existing building or structure listed in paragraph (1) of subsection (b) of
O.C.G.A. 25-2-13 and which comes under the
jurisdiction of the Office of the Safety Fire Commissioner, pursuant to
O.C.G.A. 25-2-12, shall be deemed to be a
proposed (new) building in the event such building or structure is subject to
substantial renovation, a fire or other hazard of serious consequence, or a
change in the classification of occupancy. The term "substantial renovation",
for purposes of this subsection means any construction project involving exits
or internal features of such building or structure costing more than the
building's or structure's assessed value according to county tax records at the
time of such renovation (O.C.G.A.
25-2-14). Where a change of
classification is involved, also refer to 102.3 of this
Code.
103.3 Proposed (new) buildings and additions to existing
buildings:
103.3.1 Pursuant to O.C.G.A.
25-2-14.1(b),
every proposed building and structure listed in paragraph (1) of subsection (b)
of O.C.G.A.
25-2-13shall comply with the
adopted minimum fire safety standards that were in effect on the date that
plans and specifications therefore were received by the state fire marshal, the
proper local fire marshal, or state inspector for review and approval.
103.3.2 Plans and specifications for all
proposed buildings which come under classification in paragraph (1) of
subsection (b) of O.C.G.A.
25-2-13 and which come under the
jurisdiction of the Office of the Safety Fire Commissioner pursuant to O.C.G.A.
25-2-12shall be submitted to and
receive approval by either the state fire marshal, the proper local fire
marshal, or state inspector before any state, municipal, or county building
permit may be issued or construction started (O.C.G.A.
25-2-14(a)). All
such plans and specifications submitted as required by O.C.G.A.
25-2-14(a)shall
be accompanied by a fee in the amount provided in O.C.G.A.
25-2-4.1 and shall bear the seal
and Georgia registration number of the drafting architect or engineer or shall
otherwise have the approval of the Commissioner.
103.3.3 Pursuant to O.C.G.A.
25-2-37(a), it
shall be unlawful for any person to begin construction on any proposed building
or structure which comes under the classification in paragraph (1) of
subsection (b) of O.C.G.A
25-2-13 and which comes under the
jurisdiction of the Office of the Safety Fire Commissioner pursuant to O.C.G.A.
25-2-12without first having plans
approved in accordance with O.C.G.A.
25-2-14.
103.4Proposed building construction and
completion. Pursuant to O.O.G.A. 25-2-14(b), a complete set of plans and
specifications approved as set forth in 103.3 shall be maintained on the
construction site, and construction shall proceed in compliance with the state
minimum fire safety standards under which such plans and specifications were
approved. The owner of any such building or structure or his authorized
representative shall notify the state fire marshal, the proper local fire
marshal, or state inspector upon completion of approximately 80 percent of the
construction thereof and shall apply for a certificate of occupancy when
construction of such building or structure is completed.
103.5Certificate of occupancy
required. Pursuant to O.C.G.A.
25-2-14(c), every
building or structure which comes under classification in paragraph (1) of
subsection (b) of O.C.G.A.
25-2-13 and which comes under the
jurisdiction of the Office of the Safety Fire Commissioner pursuant to O.C.G.A.
25-2-12shall have a certificate of
occupancy issued by the state fire marshal, the proper local fire marshal, or
state inspector before such building or structure may be occupied. Such
certificates of occupancy shall be issued for each business establishment
within the building, shall carry a charge in the amount provided in O.C.G.A.
25-2-4.1, shall state the occupant
load for such business establishment or building, shall be posted in a
prominent location within such business establishment or building, and shall
run for the life of the building, except as provided in O.C.G.A.
25-2-14(d). (See
103.2.1of the IFC, as adopted by this Chapter.)"
|
11. |
The provisions of section 105, PERMITS,
are not adopted for purposes of this Chapter. Local governing authorities may
adopt the provisions for local purposes. Refer to section 103.3 with regard to
permits required by the Rules and Regulations of the Safety Fire
Commissioner. |
12. |
Delete section
107.6 in its entirety and substitute in its place the following:
"107.6Overcrowding and Life Safety
Hazards. Overcrowding or admittance of any person beyond the approved
capacity of a building or a portion thereof shall not be allowed. The Fire Code
Official, upon finding any overcrowded conditions or obstructions in aisles,
passageways or other means of egress, or upon finding any condition which
constitutes a life safety hazard, shall be authorized to cause the event to be
stopped until such condition or obstruction is corrected. A structure,
building, individual room or designated portion thereof shall be deemed to be
overcrowded if the number of occupants exceeds one person per 5 sq. ft. of open
net floor area of such room or space when fixed seating is not provided. In
addition, a structure, building, room or designated portion thereof shall be
deemed overcrowded if the total number of occupants exceeds the exit capacity
of the structure, building, room or area involved."
|
13. |
The provisions of section 108, BOARD OF
APPEALS, are not adopted for purposes this Chapter. Local governing authorities
may adopt the provisions for local purposes. |
14. |
Delete section 109.3 and all sections
there under in their entirety and substitute in its place the following:
"109.3 Violation penalties. Persons who shall
violate a provision of this code or shall fail to comply with any of the
requirements thereof or who shall erect, install, alter, repair or do work in
violation of the approved construction documents or directive of the fire code
official, or of a permit or certificate used under provisions of this
Code, shall be guilty of violation of Code Section
25-2-37 of the Official Code of
Georgia Annotated. Each day that a violation continues after due notice has
been served shall be deemed a separate offense.
109.3.1 Abatement of violation. In addition to
the imposition of the penalties herein described, the fire code official is
authorized to institute appropriate action to prevent unlawful construction or
to restrain, correct or abate a violation; or to prevent illegal occupancy of a
structure or premises; or to stop an illegal act, conduct of business or
occupancy of a structure on or about any premises.
|
|
(b) |
Modifications to Chapter 2:
1. |
Delete section 201.3 in its entirety and
substitute in its place the following:
"201.3 Terms defined in other codes. Where terms
are not defined in this Code and are defined in the
International Building Code (IBC), the International
Fuel Gas Code (IFGC), the International Mechanical Code (IMC),
or codes and standards of the National Fire Protection Association
(NFPA), as adopted by this Chapter and other Rules and Regulations of the
Safety Fire Commissioner, such terms shall have the meanings ascribed to them
as in those codes and standards."
|
2. |
Add the following definitions to section
202:
"Day-care Center- A day-care facility subject to
licensure or commission by the
Department of Human Resources where more than 12 clients
receive care."
"Group Day-care Home- A day-care facility
subject to licensure or commission by the Department of Human Resources where
at least seven but not more than 12 clients receive care."
"Personal Care Home/Assisted Living Facility-
Any building or part thereof that is used for the lodging or boarding of
residents, not related by blood or marriage to the owners or operators, for the
purpose of providing personal care services and licensed as a personal care
home or assisted living facility."
"Residential Occupancies. Occupancies, as
specified in the scope of this standard, include the following, as defined in
Chapter 2 of this Code, or the IBC, or by
State law, or by the Rules and Regulations of the Georgia Safety Fire
Commissioner:
(2) |
Lodging and rooming
houses, |
(3) |
Board and care
facilities, |
(4) |
Hotels, motels, and
dormitories, |
(5) |
Personal care
homes and assisted living facilities, |
(6) |
Day-care centers and group day-care
homes." |
|
|
(c) |
Modifications to Chapter 3:
1. |
Delete section 303.5 in its entirety and substitute in its place the following:
"303.5 Fire Extinguishers. There shall be at
least one portable fire extinguisher complying with Section 906 and with a
minimum 2-A:40-B:C rating within 25 feet (7620 mm) of each asphalt (tar) kettle
during the period such kettle is being utilized, and a minimum of one
additional portable fire extinguisher with a minimum 3-A:40-B:C rating on the
roof being covered."
|
2. |
Add
new exceptions 4, 5, 6, 7 and 8 to section 308.3.7 to read as follows:
"4. In Group A public assembly occupancies
having an occupant load greater than 300, a minimum ceiling height of 25 feet
and that are protected throughout by an approved, supervised automatic
sprinkler system installed in accordance with NFPA 13, as adopted by this
Chapter, pyrotechnic special effect devices shall be permitted to be used on
stages before proximate audiences for ceremonial or religious purposes, as part
of a demonstration in exhibits, or as part of a performance, provided that
precautions satisfactory to the authority having jurisdiction are taken to
prevent ignition of any combustible material and use of the pyrotechnic device
complies with NFPA 1126, Standard for the Use of Pyrotechnics before a
Proximate Audience, as adopted by Chapter 120-3-22 Rules and
Regulations of the Safety Fire Commissioner. The ceiling height may be lowered
to a minimum of 15 feet upon approval of the authority having jurisdiction
having witnessed a demonstration shot of all types of devices being used in the
display.
5. In Group A public assembly occupancies having an occupant
load greater than 300, a minimum ceiling height of 25 feet and that are
protected throughout by an approved, supervised automatic sprinkler system
installed in accordance with NFPA 13, as adopted by this Chapter, flame effects
before an audience shall be permitted in accordance with NFPA 160,
Standard for Flame Effects Before an Audience, as adopted by
Chapter 120-3-22 Rules and Regulations of the Safety Fire Commissioner. The
ceiling height may be lowered to a minimum of 15 feet upon approval of the
authority having jurisdiction having witnessed a demonstration of all types of
devices being used in the display.
6. On stages and platforms as a necessary part of a
performance in public assembly occupancies having an occupant load greater than
300, a minimum ceiling height of 25 feet and that are protected throughout by
an approved, supervised automatic sprinkler system installed in accordance with
NFPA 13, as adopted by this Chapter. The ceiling height may be lowered to a
minimum of 15 feet upon approval of the authority having jurisdiction having
witnessed a demonstration of all types of devices being used in the
display.
7. In Group A public assembly occupancies having an occupant
load greater than 100 with fixed seating, a minimum ceiling height of 25 feet
and that have a minimum of two certified fire fighters on site with proper fire
fighting equipment as determined by the local fire official, pyrotechnic
special effect devices shall be permitted to be used on stages before proximate
audiences for ceremonial or religious purposes, as part of a demonstration in
exhibits, or as part of a performance, provided that precautions satisfactory
to the authority having jurisdiction are taken to prevent ignition of any
combustible material and use of the pyrotechnic device complies with NFPA 1126,
Standard for the Use of Pyrotechnics before a Proximate Audience,
as adopted by Chapter 120-3-22 Rules and Regulations of the Safety
Fire Commissioner. The ceiling height may be lowered to a minimum of 15 feet
upon approval of the authority having jurisdiction having witnessed a
demonstration shot of all types of devices being used in the display.
8. In public assembly occupancies having an occupant load
greater than 100 with fixed seating, a minimum ceiling height of 25 feet and
that have a minimum of two certified fire fighters on site with proper fire
fighting equipment as determined by the local fire official, flame effects
before an audience shall be permitted in accordance with NFPA 160,
Standard for Flame Effects Before an Audience, as adopted by
this Chapter. The ceiling height may be lowered to a minimum of 15 feet upon
approval of the authority having jurisdiction having witnessed a demonstration
of all types of devices being used in the display."
|
3. |
Add a new section 308.7 to read as
follows:
"308.7 Portable Cooking Equipment.
Portable cooking equipment that is not flue-connected shall be permitted only
as follows:
(1) Equipment fueled by small heat sources that can be
readily extinguished by water, such as candles or alcohol-burning equipment,
including solid alcohol, shall be permitted to be used, provided that
precautions satisfactory to the authority having jurisdiction are taken to
prevent ignition of any combustible materials.
(2) Candles shall be permitted to be used on tables used for
food service where securely supported on substantial noncombustible bases
located to avoid danger of ignition of combustible materials and only where
approved by the authority having jurisdiction.
(3) Candle flames shall be protected.
(4) "Flaming sword"or other equipment involving open flames
and flamed dishes, such as cherries jubilee or crépe suzette, shall be
permitted to be used, provided that precautions subject to the approval of the
authority having jurisdiction are taken.
(5) Listed and approved LP-Gas commercial food service
appliances shall be permitted to be used where in accordance with NFPA 58,
Liquefied Petroleum Gas Code."
|
4. |
Delete section 310.1 and all sections
there under in their entirety and substitute in its place the following:
"310.1 General. The smoking or carrying of a
lighted pipe, cigar, cigarette or any other type of smoking paraphernalia or
material is prohibited in buildings, structures, or areas, or portions of
buildings, structures, or areas, as indicated is this section, or in any other
section of this Code or in any other code or standard, as
adopted by the Rules and Regulations of the Safety Fire
Commissioner."
|
5. |
Add a new
section 316 to read as follows: "SECTION 316 LABORATORIES,
316.1 General. Laboratories in which chemicals
are used shall comply with NFPA 45, as adopted by this Chapter.
Exception: Laboratories in I-2 (healthcare)
occupancies and in medical and dental offices, shall comply with NFPA 99, as
adopted by this Chapter."
|
|
(d) |
Modifications to Chapter 4:
1. |
Add a new paragraph 4 and renumber the
remaining paragraphs in section 404.2 to read as follows:
"404.2 Where required. An approved fire safety
and evacuation plan shall be prepared and maintained for the following
occupancies and buildings.
1. Group A, other than Group A occupancies used exclusively
for purposes of religious worship that have an occupant load less than
2,000.
2. Group B buildings having an occupant load of 500 or more
persons or more than 100 persons above or be low the lowest level of exit
discharge.
3. Group E.
4. Group F.
5. Group H.
6. Group I.
7. Group R-1.
8. Group R-2 college and university buildings.
9. Group R-4.
10. High-rise buildings.
11. Group M buildings having an occupant load of 500 or more
persons or more than 100 persons above or be low the lowest level of exit
discharge.
12. Covered malls exceeding 50,000 square feet (4645 m2) in
aggregate floor area.
13. Underground buildings.
14. Buildings with an atrium and having an occupancy in Group
A, E or M."
|
2. |
Delete
section 405 and all sections there under in their entirety and substitute in
its place the following:
"SECTION 405
EMERGENCY EVACUATION DRILLS
405.1 General. Emergency evacuation drills
complying with the provisions of this section shall be conducted at least
annually in the occupancies listed in Section 404.2 or when required by the
fire code official. Drills shall be designed in cooperation with the local
authorities.
405.2 Frequency. Required emergency evacuation
drills shall be held at the intervals specified in Table 405.2 or more
frequently where necessary to familiarize all occupants with the drill
procedure.
405.3 Leadership. Responsibility for the
planning and conduct of drills shall be assigned to competent persons
designated to exercise leadership.
405.4 Time. Drills shall be held at unexpected
times and under varying conditions to simulate the unusual conditions that
occur in case of fire.
405.5 Record keeping. Records shall be
maintained on site and available for inspection by the Fire Code Official of
all required emergency evacuation drills for three years. Such records shall
include the following information:
1. Identity of the person conducting the drill.
2. Date and time of the drill.
3. Notification method used.
4. Staff members on duty and participating.
5. Number of occupants evacuated.
6. Special conditions simulated.
7. Problems encountered.
8. Weather conditions when occupants were evacuated.
9. Time required to accomplish complete evacuation. Records
of drills conducted shall be maintained
TABLE 405.2
FIRE AND EVACUATION
DRILL
FREQUENCY AND
PARTICIPATION
|
GROUP OROCCUPANCY
|
FREQUENCY
|
PARTICIPATION
|
Group A
|
Quarterly
|
Employees
|
Group Bc
|
Annually
|
Employees
|
Group Ee
|
Monthlya
|
All occupants
|
Group F & H
|
Annually on each shift
|
Employees
|
Group I
|
Quarterly on each shift
|
Employeesb
|
Group R-1
|
Quarterly on each shift
|
Employees
|
Group R-2d
|
Four annually
|
All occupants
|
Group R-4
|
Quarterly on each shift
|
Employeesb
|
High-rise buildings
|
Annually
|
Employees
|
a. The frequency shall be allowed to be modified in
accordance with Section 408.3.2.
b. Fire and evacuation drills in residential care assisted
living facilities shall include complete evacuation of the premises in
accordance with Section 408.10.5. Where occupants receive habilitation or
rehabilitation training, fire prevention and fire safety practices shall be
included as part of the training program.
c. Group B buildings having an occupant load of 500 or more
persons or more than 100 persons above or below the lowest level of exit
discharge.
d. Applicable to Group R-2 college and university buildings
in accordance with Section 408.3.
e. Drills shall be reported electronically to the Office of
the Safety Fire Commissioner.
405.6 Notification. Where required by the fire
code official, prior notification of emergency evacuation drills shall be given
to the fire code official.
405.7 Initiation. Where a fire alarm system is
provided, emergency evacuation drills shall be initiated by activating the fire
alarm system.
405.8 Accountability. As building occupants
arrive at the assembly point, efforts shall be made to determine if all
occupants have been successfully evacuated or have been accounted for.
405.9 Recall and reentry. An electrically or
mechanically operated signal used to recall occupants after an evacuation shall
be separate and distinct from the signal used to initiate the evacuation. The
recall signal initiation means shall be manually operated and under the control
of the person in charge of the premises or the official in charge of the
incident. No one shall reenter the premises until authorized to do so by the
official in charge."
|
3. |
Add
an exception to section 406.2 to read as follows:
"Exception: Child care-giver training. A minimum
of five hours initial fire safety training and recommendation for receipt of a
certificate of merit for successful completion of the training shall be
required for all directors, operators and all staff members of day-care centers
and group day-care homes as defined by the Life Safety Code adopted by this
Chapter. The curriculum for the fire safety training shall receive written
approval by the State Fire Marshal's Office and be taught by an instructor
registered with the Safety Fire Commissioner's Office. All staff members shall
receive this training within 90 days from receipt of a license, being
commissioned or the opening of a new center or home. Any new staff member shall
receive a minimum of five hours initial fire safety training and recommendation
for receipt of a certificate of merit for successful completion of the training
within 90 days of employment. In addition, a minimum of two hours fire safety
refresher training recommendation for receipt of a certificate of merit for
successful completion of the training shall be required for all directors,
operators and all staff members of day-care centers and group day-care homes
every three years from the date initial training is received. The curriculum
for the fire safety refresher training shall receive written approval by the
State Fire Marshal's Office and be taught by an instructor registered with the
Safety Fire Commissioner's Office."
|
4. |
Add new sections 408.2.3 and 408.2.3.1 to
read as follows:
"408.2.3 Crowd Managers. Assembly occupancies
having occupant loads of 100 or more shall be provided with a minimum of one
trained crowd manager or crowd manager supervisor. Where the occupant load
exceeds 250, additional trained crowd managers or crowd manager supervisors
shall be provided at a ratio of 1:250, crowd manager/supervisor to occupants,
respectively, unless otherwise permitted by the following:
(1) This requirement shall not apply to assembly occupancies
used exclusively for religious worship with an occupant load not exceeding
2000.
(2) With the exception of assembly occupancies noted above
where alcoholic beverages are consumed, the ratio of trained crowd managers to
occupants shall be permitted to be reduced where, in the opinion of the
authority having jurisdiction, the existence of an approved, supervised
sprinkler system and the nature of the event warrant.
408.2.3.1 The crowd manager shall receive
approved training in crowd management techniques."
|
5. |
Delete sections 408.4 through 408.11 all
sections there under in their entirety and substitute in their place the
following:
"408.4 Group F occupancies. Group F occupancies
shall comply with the requirements of Sections 408.4.1 through 408.4.4 and
Sections 401 through 407.
408.4.1 Plans and diagrams. In addition to the
requirements of Section 404 and Section 407.6, plans and diagrams shall be
maintained in approved locations indicating any hazardous areas within the
facility and locations of exits.
408.4.2 Plan updating. The plans and diagrams
required by Section 408.4.1 shall be maintained up to date and the fire code
official and fire department shall be informed of all major changes.
408.4.3 Emergency response team. Responsible
persons shall be designated as the on-site emergency response team and trained
to be liaison personnel for the fire department. These persons shall aid the
fire department in preplanning emergency responses, identifying hazardous
locations and be familiar with the chemical nature of any hazardous material
stored on site. An adequate number of personnel for each work shift shall be
designated.
408.4.3.1 Disaster training. Malfunctions of
the process should be simulated and emergency actions undertaken. Disaster
drills that simulate a major catastrophic situation should be undertaken
periodically with the cooperation and participation of public fire, police, and
other local community emergency units nearby cooperating plants if
involved.
408.4.4 Employee Training. The requirements of
Sections 408.4.4.1 thru 408.4.6 shall be for new employees and shall be also be
applied retroactively with a completion date of January 1, 2011, for existing
employees.
408.4.4.1 Initial Training. Initial training
shall be provided to employees and contractors who are involved in operating,
maintaining, and supervising facilities that handle combustible particulate
solids. Initial training shall ensure that all employees are knowledgeable
about the following:
(1) Hazards of their workplace
(2) General orientation, including plant safety rules
(3) Process description
(4) Equipment operation, safe startup and shutdown, and
response to upset conditions
(5) The necessity for proper functioning of related fire and
explosion protection systems
(6) Equipment maintenance requirements and practices
(7) Housekeeping requirements
(8) Emergency response plans
408.4.4.2 Re fresher Training. Emergency plans
and procedures, including information that is covered in Section 408.4.4.1,
shall be provided to and reviewed annually by all employees and contractors who
are involved in operating, maintaining, and supervising facilities that handle
combustible particulate solids.
408.4.5 Notification of Hazards. Notification
of hazards shall be by means of internal written or electronic correspondence,
postings of information at conspicuous locations and/or by other means to
disseminate information to employees to ensure they are knowledgeable about the
hazards of their workplace. Required notifications shall include such topics as
prescribed in 408.4.4.1.
408.4.5.1 Notification Frequency. All employees
shall receive monthly notification of hazards and safety information related to
the industry's operation.
408.4.6 Certification. For those industries
having operations involving the manufacturing, processing, and/or handling
combustible particulate solids including manufacturing processes that create
combustible dust listed under Rule
120-3-24-.02(1)(b),
the employer's authorized agent shall electronically file to the Safety Fire
Commissioner a written affidavit certifying annually that the training and
monthly notifications required by Section 408.4.4.1 have been completed for the
past calendar year.
408.4.7 Emergency drills. Emergency drills of
the on-site emergency response team shall be conducted on a regular basis but
not less than once annually. Records of drills conducted shall be maintained on
site and available for inspection by the Fire Code Official.
408.5 Group H occupancies. Group H occupancies
shall comply with the requirements of Sections 408.5.1 through 408.5.4 and
Sections 401 through 407.
408.5.1 Plans and diagrams. In addition to the
requirements of Section 404 and Section 407.6, plans and diagrams shall be
maintained in approved locations indicating the approximate plan for each area,
the amount and type of HPM stored, handled and used, locations of shutoff
valves for HPM supply piping, emergency telephone locations and locations of
exits.
408.5.2 Plan updating. The plans and diagrams
required by Section 408.5.1 shall be maintained up to date and the fire code
official and fire department shall be informed of all major changes.
408.5.3 Emergency response team. Responsible
persons shall be designated as the on-site emergency response team and trained
to be liaison personnel for the fire department. These persons shall aid the
fire department in preplanning emergency responses, identifying locations where
HPM is stored, handled and used, and be familiar with the chemical nature of
such material. An adequate number of personnel for each work shift shall be
designated.
408.5.3.1Disaster training.
Malfunctions of the process should be simulated and emergency actions
undertaken. Disaster drills that simulate a major catastrophic situation should
be undertaken periodically with the cooperation and participation of public
fire, police, and other local community emergency units nearby cooperating
plants if involved.
408.5.4Employee Training. The
requirements of Sections 408.5.4.1 thru 408.5.6 shall be for new employees and
shall be also be applied retroactively with a completion date of January 1,
2011, for currently existing employees.
408.5.4.1Initial Training. Initial
training shall be provided to employees who are involved in operating,
maintaining, and supervising facilities that handle combustible particulate
solids. Initial training shall ensure that all employees are knowledgeable
about the following:
(1) Hazards of their workplace
(2) General orientation, including plant safety rules
(3) Process description
(4) Equipment operation, safe startup and shutdown, and
response to upset conditions
(5) The necessity for proper functioning of related fire and
explosion protection systems
(6) Equipment maintenance requirements and practices
(7) Housekeeping requirements
(8) Emergency response plans
408.5.5Notification of Hazards.
All employees shall receive monthly notification of hazards and safety
information related to the industry's operation.
408.5.5.1Notification Frequency.
Notification of hazards shall be by means of internal written or electronic
correspondence, postings of information at conspicuous locations and/or by
other means to disseminate information to employees to ensure they are
knowledgeable about the hazards of their workplace. Monthly notifications can
include such topics as prescribed in 408.5.4.1.
408.5.6Certification. For those
industries having operations involving the manufacturing, processing, and/or
handling combustible particulate solids including manufacturing processes that
create combustible dust listed under Rule
120-3-24-.02(1)(b),
the employer's authorized agent shall electronically file to the Safety Fire
Commissioner a written affidavit certifying annually that the training and
monthly notifications required by Section 408.5.4.1 have been completed for the
past calendar year.
408.5.7Emergency drills. Emergency
drills of the on-site emergency response team shall be conducted on a regular
basis but not less than once every three months. Records of drills conducted
shall be maintained and available for inspection by the Fire Code
Official.
408.6Group I-1 occupancies. Group
I-1 occupancies shall comply with the requirements of Sections 408.6.1 through
408.6.5 and Sections 401 through 406.
408.6.1Fire safety and evacuation
plan. The fire safety and evacuation plan required by Section 404 shall
include special staff actions including fire protection procedures necessary
for residents and shall be amended or revised upon admission of any resident
with unusual needs.
408.6.2Staff training. Employees
shall be periodically instructed and kept informed of their duties and
responsibilities under the plan. Such instruction shall be reviewed by the
staff at least every two months. A copy of the plan shall be readily available
at all times within the facility.
408.6.3Resident training.
Residents capable of assisting in their own evacuation shall be trained in the
proper actions to take in the event of a fire. The training shall include
actions to take if the primary escape route is blocked. Where the resident is
given rehabilitation or habilitation training, training in fire prevention and
actions to take in the event of a fire shall be a part of the rehabilitation
training program.
Residents shall be trained to assist each other in case of
fire to the extent their physical and mental abilities permit them to do so
without additional personal risk.
408.6.4Drill frequency. Emergency
evacuation drills shall be conducted at least six times per year, two times per
year on each shift. Twelve drills shall be conducted in the first year of
operation. Drills are not required to comply with the time requirements of
Section 405.4.
408.6.5Resident participation.
Emergency evacuation drills shall involve the actual evacuation of residents to
a selected assembly point.
Exception: Actual exiting from windows shall not
be required. Where a drill scenario includes the escape from windows, Opening
the window and signaling for assistance shall be acceptable.
408.7Group I-2 occupancies. Group
I-2 occupancies shall comply with the requirements of Sections 408.7.1 and
408.7.2 and Sections 401 through 406. Drills are not required to comply with
the time requirements of Section 405.4.
408.7.1 Evacuation not required. During
emergency evacuation drills, the movement of patients to safe areas or to the
exterior of the building is not required.
408.7.2 Coded alarm signal. When emergency
evacuation drills are conducted after visiting hours or when patients or
residents are expected to be asleep, a coded announcement is allowed instead of
audible alarms.
408.8 Group I-3 occupancies. Group I-3
occupancies shall comply with the requirements of Sections 408.8.1 through
408.8.4 and Sections 401 through 406.
408.8.1 Employee training. Employees shall be
instructed in the proper use of portable fire extinguishers and other manual
fire suppression equipment. Training of new staff shall be provided promptly
upon entrance on duty. Refresher training shall be provided at least
annually.
408.8.2 Staffing. Group I-3 occupancies shall
be provided with 24-hour staffing. Staff shall be within three floors or 300
feet (9144 mm) horizontal distance of the access door of each resident housing
area. In Use Conditions 3, 4 and 5, as defined in Chapter 2, the arrangement
shall be such that the staff involved can start release of locks necessary for
emergency evacuation or rescue and initiate other necessary emergency actions
within 2 minutes of an alarm.
Exception: Staff shall not be required to be
within three floors or 300 feet (9144 mm) in areas in which all locks are
unlocked remotely and automatically in accordance with Section 408.4 of the
International Building Code.
408.8.3 Notification. Provisions shall be made
for residents in Use Conditions 3, 4 and 5, as defined in Chapter 2, to readily
notify staff of an emergency.
408.8.4 Keys. Keys necessary for unlocking
doors installed in a means of egress shall be individually identifiable by both
touch and sight.
408.9 Group R-1 occupancies. Group R-1
occupancies shall comply with the requirements of Sections 408.8.1 through
408.8.3 and Sections 401 through 406.
408.9.1 Evacuation diagrams. A diagram
depicting two evacuation routes shall be posted on or immediately adjacent to
every required egress door from each hotel, motel or dormitory sleeping
unit.
408.9.2 Emergency duties. Upon discovery of a
fire or suspected fire, hotel, motel and dormitory employees shall perform the
following duties:
1. Activate the fire alarm system, where provided.
2. Notify the public fire department.
3. Take other action as previously instructed.
408.9.3 Fire safety and evacuation
instructions. Information shall be provided in the fire safety and
evacuation plan required by Section 404 to allow guests to decide whether to
evacuate to the outside, evacuate to an area of refuge, remain in place, or any
combination of the three.
408.10 Group R-2 occupancies. Group R-2
occupancies shall comply with the requirements of Sections 408.10.1 through
408.10.3 and Sections 401 through 406.
408.10.1 Emergency guide. A fire emergency
guide shall be provided which describes the location, function and use of fire
protection equipment and appliances accessible to residents, including fire
alarm systems, smoke alarms, and portable fire extinguishers. The guide shall
also include an emergency evacuation plan for each dwelling unit.
408.10.2 Maintenance. Emergency guides shall be
reviewed and approved in accordance with Section 401.2.
408.10.3 Distribution. A copy of the emergency
guide shall be given to each tenant prior to initial occupancy.
408.11 Group R-4 occupancies. Group R-4
occupancies shall comply with the requirements of Sections 408.11.1 through
408.11.5 and Sections 401 through 406.
408.11.1 Fire safety and evacuation plan. The
fire safety and evacuation plan required by Section 404 shall include special
staff actions, including fire protection procedures necessary for residents,
and shall be amended or revised upon admission of a resident with unusual
needs.
408.11.2 Staff training. Employees shall be
periodically instructed and kept informed of their duties and responsibilities
under the plan. Such instruction shall be reviewed by the staff at least every
two months. A copy of the plan shall be readily available at all times within
the facility.
408.11.3 Resident training. Residents capable
of assisting in their own evacuation shall be trained in the proper actions to
take in the event of a fire. The training shall include actions to take if the
primary escape route is blocked. Where the resident is given rehabilitation or
habilitation training, training in fire prevention and actions to take in the
event of a fire shall be a part of the rehabilitation training program.
Residents shall be trained to assist each other in case of fire to the extent
their physical and mental abilities permit them to do so without additional
personal risk.
408.11.4 Drill frequency. Emergency evacuation
drills shall be conducted a total of six times per year, two of which occur
twice a year on each shift. Twelve drills shall be conducted in the first year
of operation. Drills are not required to comply with the time requirements of
Section 405.4.
408.11.5 Resident participation. Emergency
evacuation drills shall involve the actual evacuation of residents to a
selected assembly point and shall provide residents with experience in exiting
through all required exits. All required exits shall be used during emergency
evacuation drills.
Exception:Actual exiting from windows shall not
be required. Opening the window and signaling for help shall be an acceptable
alternative.
408.12 Covered mall buildings. Covered mall
buildings shall comply with the provisions of Sections 408.12.1 through
408.12.3.
408.12.1 Lease plan. A lease plan shall be
prepared for each covered mall building. The plan shall include the following
information in addition to that required by Section 404.3.2:
1. Each occupancy, including identification of tenant.
2. Exits from each tenant space.
3. Fire protection features, including the following:
3.1. Fire department connections.
3.2. Fire command center.
3.3. Smoke management system controls.
3.4. Elevators and elevator controls.
3.5. Hose valves outlets.
3.6. Sprinkler and standpipe control valves.
3.7. Automatic fire-extinguishing system areas.
3.8. Automatic fire detector zones.
3.9. Fire barriers.
408.12.1.1 Approval. The lease plan shall be
submitted to the fire code official for approval, and shall be maintained on
site for immediate reference by responding fire service personnel.
408.12.1.2 Revisions. The lease plans shall be
revised annually or as often as necessary to keep them current. Modifications
or changes in tenants or occupancies shall not be made without prior approval
of the fire code official and building official.
408.12.2 Tenant identification. Each occupied
tenant space provided with a secondary exit to the exterior or exit corridor
shall be provided with tenant identification by business name and/or address.
Letters and numbers shall be posted on the corridor side of the door, be
plainly legible and shall contrast with their background.
Exception:Tenant identification is not required
for anchor stores.
408.12.3 Maintenance. Unoccupied tenant spaces
shall be:
1. Kept free from the storage of any materials.
2. Separated from the remainder of the building by partitions
of at least 0.5-inch-thick (12.7 mm) gypsum board or an approved equivalent to
the underside of the ceiling of the adjoining tenant spaces.
3. Without doors or other access openings other than one door
that shall be kept key locked in the closed position except during that time
when opened for inspection.
4. Kept free from combustible waste and be broom swept
clean."
|
|
(e) |
Modifications to Chapter 5:
1. |
Add a new section 501.5 to read as
follows:
"501.5 Where buildings or facilities fall under
the jurisdiction of the Georgia Safety Fire Commissioner as set forth in the
Official Code of Georgia Annotated (O.C.G.A.), Title 25, Chapter 2, except for
State owned facilities, it is intended that the provisions of Chapter 5 that
primarily relate to fire department response, access to facilities, access to
building interiors, key boxes, premises identification, fire department
connection locations, and fire hydrant locations be administered by the local
Fire Chief and/or Fire Code Official responsible for providing fire or other
emergency response to the buildings or facilities. With regard to State owned
facilities, that are not provided with a facility fire department, it is
intended that the local Fire Chief and/or Fire Code Official have input in the
planning of facilities with regard to the noted provisions covered by Chapter
5."
|
2. |
Delete section 503.1.1
in its entirety and substitute in its place the following:
"503.1.1 Buildings and facilities. Approved fire
apparatus access roads shall be provided for every facility, building or
portion of a building hereafter constructed or moved into or within the
jurisdiction as determined by the local Fire Chief and/or Fire Code Official of
the responding fire department or agency. The fire apparatus access road shall
comply with the requirements of this section and shall extend to within 150
feet (45.7 m) of all portions of the facility or any portion of the exterior
wall of the first story of the building as measured by an approved route around
the exterior of the building or facility."
"Exception:The local Fire Chief and/or Fire Code
Official of the responding fire department or agency is authorized to increase
the dimension of 150 feet (45.7 m) where:
"1. The building is equipped throughout with an approved
automatic sprinkler system installed in accordance with Section 903.3.1.1,
903.3.1.2 or 903.3.1.3.
"2. Fire apparatus access roads cannot be installed because
of location on property, topography, waterways, nonnegotiable grades or other
similar conditions, and an approved alternative means of fire protection is
provided.
"3. There are not more than two Group R-3 or Group U
occupancies."
|
3. |
Add a new
section 504.1.1 to read as follows:
"504.1.1 Access Doors. For fire fighting
purposes, there shall be at least one access door in each 100 linear feet (30.5
m) or major fraction thereof of the exterior walls which face the access
roadways required by Section 503, unless otherwise required in this code
section. In exterior walls designed with continuous rolling dock doors, which
face access roadways, there shall be at least one access door in each 200
linear feet (61 m) or fraction thereof. Required access doors shall be a
minimum of 3 feet (0.9 m) wide and 6 feet 8 inches (2 m) high and shall be
accessible without use of a ladder. Rolling doors are acceptable for such
purposes in buildings protected throughout by an approved automatic sprinkler
system(s) unless otherwise approved for unsprinklered buildings by the local
Fire Chief and /or Fire Code Official."
|
4. |
Delete section 508.5.1 in its entirety and
substitute in its place the following:
"508.5.1 Where required. Where a portion of the
facility or building hereafter constructed or moved into or within the
jurisdiction is more than 500 feet (152 m) from a hydrant on a fire apparatus
access road, as measured by an approved route around the exterior of the
facility or building, on-site fire hydrant mains shall be provided where
required by the local Fire Chief and/or Fire Code Official of the responding
fire department or agency.
"Exceptions:
"1. For group R-3 and Group U occupancies, the distance
requirement shall be 600 feet (183 m).
"2. For buildings equipped throughout with an approved
automatic sprinkler system installed in accordance with Section 903.3.1.1 or
903.3.1.2, the distance requirement shall be 600 feet (183
m)."
|
|
(f) |
Modifications to Chapter 6:
1. |
Add a new section 601.3 to read as follows:
"601.3 Where reference is made in this
Code to the International Electrical Code, it
shall be construed as referencing NFPA 70, National Electrical Code
(NEC) as adopted by this Chapter."
|
2. |
Delete section 603.1.4 in its entirety and
substitute in its place the following:
"603.1.4 Fuel Oil. The grade of fuel oil used
in a burner shall be that for which the burner is approved and as stipulated by
the manufacturer. The use of crankcase oil or any other oil containing gasoline
shall not be used except as permitted in NFPA 31, Standard for the
Installation of Oil-Burning Equipment, as adopted by Chapter 120-3-11,
Rules and Regulations of the Safety Fire Commissioner."
|
3. |
Delete section 603.4 in its entirety and
substitute in its place the following. Section 603.4.1 remains unchanged.
"603.4 Portable heaters. Liquefied petroleum gas
fuel fired, or liquid fuel fired space heating devices designed to be portable
are prohibited in all portions of occupancies in Groups A, E, F, I, R-1, R-2,
R-3 and R-4.
Exceptions:
1. In emergency conditions, when approved by the authority
having jurisdiction, equipment designed to be portable may be used for a
specified time provided such equipment is properly protected and separated from
combustibles as specified by the manufacturer's instructions and the authority
having jurisdiction.
2. Listed and approved unvented fuel-fired heaters in one-
and two- family dwellings and portable outdoor gas-fired heating appliances
used outside one- and two-family dwellings.
3. Portable outdoor gas-fired heating appliances are allowed
in accordance with Section 603.4.2."
4. Add a new section 603.4.2 to read as follows:
603.4.2Portable outdoor gas-fired heating
appliances. Portable gas-fired heating appliances located outdoors shall
be in accordance with Sections 603.4.2.1 through 603.4.2.3.4.
603.4.2.1Location. Portable
outdoor gas-fired heating appliances shall be located in accordance with
Sections 603.4.2.1.1 through 603.4.2.1.4.
603.4.2.1.1Prohibited locations.
The storage or use of portable outdoor gas-fired heating appliances is
prohibited where any of the following exist:
1. Inside any occupancy when connected to the fuel gas
container.
2. Inside tents, canopies and membrane structures.
3. On exterior balconies in accordance with NFPA 58.
603.4.2.1.2 Clearance to buildings. Portable
outdoor gas-fired heating appliances shall be located at least 5 feet from
buildings.
603.4.2.1.3 Clearance to combustible materials.
No portion of portable outdoor gas-fired heating appliances shall be located
beneath, or closer than 5 feet to combustible overhangs, awnings, sunshades or
similar combustible attachments buildings and combustible decorations.
603.4.2.1.4 Proximity to exits. Portable
outdoor gas-fired heating appliances shall not be located within 10 feet of
exits or exit discharges.
603.4.2.2 Installation and operation. Portable
outdoor gas-fired heating appliances shall be installed and operated in
accordance with Sections 603.4.2.2.1 through 603.4.2.2.4.
603.4.2.2.1 Listing and approval. Only listed
and approved heating appliances utilizing a fuel gas container that is integral
to the appliance shall be used.
603.4.2.2.2 Installation and
maintenancePortable outdoor gas-fired heating appliances shall be
installed and maintained in accordance with the manufacturer's
instructions.
603.4.2.2.3 Tip-over switch. Portable gas-fired
heating appliances shall be equipped with a tilt or tip-over switch that
automatically shuts off the flow of gas if the appliance is tilted more than 15
degrees from vertical.
603.4.2.2.4 Guard against contact. The heating
element or combustion chamber shall be permanently guarded so as to prevent
accidental contact by persons or material.
603.4.2.3 Gas container. Fuel gas containers
for portable outdoor gas-fired heating appliances shall comply with Sections
603.4.2.3.1 through 603.4.2.3.4.
603.4.2.3.1 Approved containers. Only approved
U.S. DOT or ASME gas containers shall be used.
603.4.2.3.2 Container replacement. Replacement
of gas containers in the heating appliance shall not be conducted while the
public is present.
603.4.2.3.3 Container capacity. The maximum
individual capacity of gas containers used in connection with portable
gas-fired heating appliances shall not exceed 20 pounds.
603.4.2.3.4 Indoor storage prohibited. Gas
containers shall not be stored inside of buildings except in accordance with
Section 3809.9."
5. Delete section 605.10 and substitute in its place the
following: Sections 605.10.1 through 605.10.4 remain unchanged.
"605.10Portable, electric space heaters.Portable, electric heaters are prohibited in all portions of occupancies
in Groups A, E, F, R-1, R-2, and R-4. Where permitted, portable electric space
heaters shall comply with Sections 605.10.1 through 605.10.4."
6. Add a new section 605.11 to read as follows:
"605.11 Separation from Transformers.Space separation for transformers shall be as follows:
"(1) Transformer pad locations shall be a minimum of 10 feet
(3 m) from any building, building overhangs, canopies, exterior walls,
balconies, exterior stairs and/or walkways connected to the building.
"(2) Transformer pad edges shall be not less than 14 feet
(4.3 m) from any doorway.
"(3) Transformer pad edges shall be not less than 10 feet (3
m) from any window or other opening.
"(4) If the building has an overhang, the 10 foot (3 m)
clearance shall be measured from a point below the edge of the overhang only if
the building is three stories or less. If the building is four stories or more,
the 10 foot (3 m) clearance shall be measured from the outside building
wall.
"(5) Fire escapes, outside stairs, and covered walkways
attached to or between buildings, shall be considered as part of the building.
"Exception No. 1: For (1), transformer pads may be
located closer to noncombustible walls than the above required minimum
clearances upon written approval of the authority having jurisdiction, however,
in no case shall the transformer location be less then 3 feet (0.9 m) from the
building.
"Exception No. 2: Transformer pads existing prior to
December 31, 1994, are exempted from this requirement. When buildings are
modified, reductions in space separations may be less than the above required
minimum clearances upon written approval of the authority having
jurisdiction."
7. Delete sections 609.1 and 609.2 in their entirety and
substitute in their place the following:
"609.1 General.Commercial kitchen
exhaust hoods and residential cooking appliances in commercial and public
buildings shall comply with the requirements of NFPA 96, Standard for
Ventilation Control and Fire Protection of Commercial Cooking Operations,
as adopted by this Chapter.
8. Delete section 609.2 in its entirety and substitute in its
place the following:
"609.2 Where required.A commercial
hood complying with NFPA 96 shall be installed at or above all commercial
cooking appliances and domestic cooking appliances used for commercial purposes
that produce grease laden vapors.
Exception:Except as provided for in the scoping
provisions subsection 1.1.4 of NFPA 96 as adopted by this
Chapter."
|
|
(g) |
Modifications to Chapter 7:
1. |
Add a new section 703.5 to read as follows:
"703.5 Barrier Identification. All fire and/or
smoke barriers or walls shall be effectively and permanently identified with
signs or stenciling above a decorative ceiling and/or in concealed spaces with
letters a minimum of 2 inches (51 mm) high on a contrasting background spaced a
maximum of 12 feet (3.7 m) on center with a minimum of one per wall or barrier.
The hourly rating shall be included on all rated barriers or walls. Suggested
wording '(__) Hour Fire and Smoke Barrier-Protect All Openings.'
"Exception:Existing stenciling acceptable to the authority having
jurisdiction."
|
2. |
Delete
section 704.1 in its entirety and substitute in its place the following:
"704.1 Enclosures. The provisions of NFPA 101 as
adopted by this Chapter shall govern the enclosures requirements of vertical
shafts, including but not limited to stairways and service and utility shafts.
(Refer to Table 102.10, CODES REFERENCE GUIDE)"
|
3. |
Delete Table 704.1 in its
entirety. |
4. |
Delete section 704.2
in its entirety and substitute in its place the following:
"704.2 Opening protectives. The provisions of
NFPA 101, Life Safety Code, as adopted by this Chapter, shall
govern the protection of openings in fire rated enclosures and barriers,
including the self-closing or automatic closing of opening
protectives."
|
|
(h) |
Modifications to Chapter 8:
1. |
Delete section 801.1 in its entirety and substitute in its place the following:
"SECTION 801 GENERAL, 801.1 Scope. The
provisions of NFPA 101, Life SafetyCode, as
adopted by this Chapter, shall govern interior finish and interior trim in
proposed (new) and existing buildings. Sections 805, 806, 807, and 808 of this
Code shall govern decorative vegetation, decorative materials
other than decorative vegetation, and furniture and furnishings in proposed
(new) and existing buildings. (Refer toTable102.10, CODES
REFERENCE GUIDE)"
|
|
(i) |
Modifications to Chapter 9:
1. |
Delete section 901.4.2 in its entirety and
substitute in its place the following:
"901.4.2Provisions in excess of the minimum Code
requirements shall, as a minimum, be installed to meet the provisions
of the currently adopted code(s) and/or standard(s) which may be applicable to
the provision at the time of its installation. Any non-required fire protection
system which is added onto, or interconnected with, any required fire
protection system (of a similar type), shall be designed, installed, and
maintained in accordance with the provisions of the currently adopted code(s)
and/or standard(s) which may be applicable to the provision at the time of its
installation.
"Exceptions:
"1. Other installations not conforming with the provisions of
the currently adopted code(s) and/or standard(s) applicable to the provision at
the time of its installation if such installations are reported and filed with
the local responding fire department and the authority having jurisdiction. In
addition such systems shall be identified as required by the authority having
jurisdiction.
"2. Non-required systems designed, reviewed, installed and
approved in accordance with local codes and/or ordinances."
|
2. |
Add a new section 901.6.3 to read as
follows:
"901.6.3 Automatic sprinkler systems and other
water based fire extinguishing systems, including fire pumps, required or
installed, shall be maintained in accordance with NFPA 25, Standard for
the Inspection, Testing, and Maintenance of Water-Based Fire Protection
Systems, adopted by this Chapter. A certificate of inspection, as
specified by NFPA 25, shall be retained on file at the facility and shall be
made available to the Fire Code Official upon request for review for a period
of at least three years."
|
3. |
Delete section 901.7.2 and substitute in its place the following:
"901.7.2 Tag Required.
(a) A tag shall be used to indicate that a system, or portion
thereof, has been removed from service.
(b) For water based fire protection systems the tagging
provisions of NFPA 25, Standard for the Inspection, Testing, and
Maintenance of Water-Based Fire Protection Systems, as adopted by this
shall apply."
|
4. |
Delete
section 903.2 in its entirety and substitute in its place the following:
"903.2 Where required. (a) Approved automatic
sprinkler systems for proposed (new) and existing buildings and structures
shall be installed as required by the applicable provisions of NFPA
101, Life Safety Code, as adopted by this Chapter, provided,
however, the International Building Code shall govern the
requirements for sprinkler protection that is related to minimum building
construction types. (Refer toTable 102.10, CODES REFERENCE GUIDE)
In addition, an automatic sprinkler system may be required by other NFPA
standards adopted by this Chapter or other Rules and Regulations of the Safety
Fire Commissioner."
Exception:Spaces or areas in telecommunications
buildings used exclusively for telecommunications equipment, associated
electrical power distribution equipment, batteries and standby engines,
provided those spaces or areas are equipped throughout with a supervised
automatic fire alarm system, and are separated from the remainder of the
building by fire barriers consisting of walls and floor/ceiling assemblies
having a fire resistance rating of not less than 2-hours.
NOTE:NFPA 76, Recommended Practice for
the Fire Protection of Telecommunications Facilities, should be
consulted. Refer to the edition adopted as a recommended practice by this
Chapter."
|
5. |
Add a new
section 903.2.1 to read as follows:
"903.2.1 The requirements for the installation,
design, and testing of automatic sprinkler systems shall be as applicable, NFPA
13, Standard for the Installation of Sprinkler Systems, NFPA
13D, Standard for the Installation of Sprinkler Systems in One- and
Two-Family Dwellings and Manufactured Homes, or NFPA 13R,
Standard for the Installation of Sprinkler Systems in Residential
Occupancies up to and Including Four Stories in Height, as adopted and
modified by this Chapter."
|
6. |
Delete section 904.2.1 in its entirety and
substitute in its place the following:
"904.2.1Commercial hood and duct systems. Each
required commercial kitchen exhaust hood and duct system required by Section
610 to have a commercial hood complying with NFPA 96 shall be protected with an
approved automatic fire-extinguishing system installed in accordance with this
code."
|
7. |
Delete section
904.11 in its entirety and substitute in its place the following: "904.11 Fire
Protection for Cooking Operations."
"904.11.1 The requirements for as well as the
design, installation, protection and maintenance of cooking equipment, shall be
as required by NFPA 101, Life Safety Code and NFPA 96,
Standard for the Ventilation Control and Fire Protection of Commercial
Cooking Operations, as adopted by this Chapter. (Refer to Table
102.10, CODES REFERENCE GUIDE)"
"904.11.2 Fire suppression systems approved for
the protection of commercial cooking equipment shall be designed, installed,
and maintained in accordance with the applicable standards adopted in this
Chapter."
|
8. |
Delete section
905.1 in its entirety and substitute in its place the following:
"905.1General. The State's minimum requirements
for standpipe systems shall be as required by this Code, and
the International Building Code. Standpipe systems shall be
designed, installed and tested in accordance with NFPA 14, Standard for
the Installation of Standpipe, and Hose Systems as adopted by this
Chapter. (Refer to Table 102.10, CODE REFERENCE GUIDE)"
|
9. |
Delete section 906.1 in its entirety and
substitute in its place the following:
"906.1Portable Fire Extinguishers - General.
Portable fire extinguishers shall be installed in all buildings, structures and
facilities falling under this Code and O.C.G.A.
25-2. For any other building,
structure, facility, or condition or special hazard, portable fire
extinguishers shall be provided as may be required by this Code
in Table 906.1, or by various codes and standards adopted by this
Chapter. (Refer to Table 102.10, CODES REFERENCE GUIDE)."
|
10. |
Delete section 906.2 in its entirety and
substitute in its place the following:
"906.2General requirements. The selection,
distribution, installation, and maintenance of portable fire extinguishers
shall comply with NFPA 10, Standard for Portable Fire
Extinguishers, as adopted by this Chapter.
Exceptions:
"1. The maximum travel distance to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies."
2. Thirty-day inspections shall not be required and
maintenance shall be allowed to be once every three years for dry-chemical or
halogenated agent portable fire extinguishers that are supervised by a listed
and approved electronic monitoring device, provided that all of the following
conditions are met:
(a) Electronic monitoring shall confirm that extinguishers
are properly positioned, properly charged and unobstructed.
(b) Loss of power or circuit continuity to the electronic
monitoring device shall initiate a trouble signal.
(c) The extinguishers shall be installed inside of a building
or cabinet in a noncorrosive environment.
(d) Electronic monitoring devices and supervisory circuits
shall be tested every three years when extinguisher maintenance is
performed.
(e) A written log of required hydrostatic test dates for
extinguishers shall be maintained by the owner to ensure that hydrostatic tests
are conducted at the frequency required by NFPA 10.
3. In Group E occupancies, in lieu of locating fire
extinguishers in corridors and normal paths of travel as specified in NFPA 10,
Standard for Portable Fire Extinguishers, fire extinguishers
may be located in rooms that open directly onto such corridors and pathways
provided all of the following are met:
(a) The room in which such extinguishers are placed are
located in close proximity to that portion of the corridor where a fire
extinguisher would otherwise be placed in accordance with NFPA 10;
Standard for Portable Fire Extinguishers,
(b) A sign which states in white letters at least one inch in
height on a red background, 'FIRE EXTINGUISHER LOCATED IN THIS ROOM,' is placed
on the corridor wall immediately adjacent to the entrance way of each such room
so that it can be clearly seen at all times;
(c) The rooms in which such extinguishers are placed shall be
constantly supervised during school hours; and
(d) Those rooms cannot be subject to being locked at any time
the building is occupied."
|
11. |
Delete section 906.9 in its entirety and
substitute in its place the following:
"906.9Height above floor. Portable fire
extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be
installed so that its top is not more than 54 inches and not less than 48
inches above the floor. Hand-held portable fire extinguishers having a gross
weight exceeding 40 pounds (18 kg) shall be installed so that its top is mot
more than 3.5 feet (1067 mm) above the floor. The clearance between the floor
and the bottom of installed hand-held extinguishers shall not be less than 4
inches (102mm)."
|
12. |
Delete
section 907.1 in its entirety and substitute in its place the following, while
retaining existing subsections:
"907.1 Fire Alarm Systems - General. The State's
minimum requirements for fire alarm systems shall be as required by NFPA 101,
Life Safety Code as adopted by this Chapter.
Fire alarm systems shall be installed, tested, and maintained in
accordance with NFPA 72, National Fire Alarm Code, as adopted
by this Chapter."
|
13. |
Delete sections 907.2 through 907.16 in their entirety and without
substitution. |
14. |
Delete section
909.1 in its entirety and substitute in its place the following:
"909.1 Scope and purpose.This
section applies to mechanical or passive smoke control systems when they are
required for proposed (new) buildings or portions thereof by provisions of the
Life Safety Code (LSC) or this Code, as
adopted by this Chapter, or by provisions of the International Building
Code (IBC), as adopted by the Department of Community Affairs,
The purpose of this section is to establish minimum requirements for
the design, installation, and acceptance testing of smoke control systems that
are intended to provide a tenable environment for the evacuation or relocation
of occupants. These provisions are not intended for the preservation of
contents, the timely restoration of operations, or for assistance in fire
suppression or overhaul activities. Smoke control systems regulated by this
section serve a different purpose than the smoke- and heat-venting provisions
found in Section 910. Mechanical smoke control systems shall not be considered
exhaust systems under Chapter 5 of the International Mechanical Code
(IMC)."
|
15. |
Delete section
909.2 in its entirety and substitute in its place the following:
"909.2 General design requirements. Buildings,
structures, or portions thereof required by provisions of the Life
Safety Code (LSC) or this Code, as adopted by this
Chapter, or by provisions of the International Building Code,
as adopted by the Department of Community Affairs, to have a smoke
control system or systems shall have such systems designed in accordance with
the applicable requirements of Section 909 of this Code and
the generally accepted and well established principles of engineering relevant
to the design. The construction documents shall include sufficient information
and detail to describe adequately the elements of the design necessary for the
proper implementation of the smoke control systems. These documents shall be
accompanied with sufficient information and analysis to demonstrate compliance
with these provisions."
|
16. |
Add a new section 909.2.1 to read as follows:
"909.2.1 Smoke Control. For the purposes
of 909.2 the following publications shall be considered as providing the
generally accepted and well established principals of engineering relevant to
design of required smoke control systems.
(1) NFPA 92A, Standard for Smoke Control Systems
Utilizing Barriers and Pressure Differences
(2) NFPA 92B, Standard for Smoke Management Systems
in Malls, Atria, and Large Areas
(3) NFPA SPP-53, Smoke Control in Fire Safety
Design
(4) ASHRAE/SFPE, Design of Smoke Management
Systems
(5) ASHRAE, Guideline 5: Guideline for Commissioning
Smoke Management Systems"
(6) NFPA 101, Life Safety Code (For
non-mandatory guidance involving systems for existing detention and correction
facilities refer to A.23.3.1.3 of the 2000 Edition)
|
17. |
Add a new section 914.7.3 to read as
follows:
"914.7.3 Limited Use Special Amusement
Buildings: Special amusement buildings not open to the public in excess
of 45 days shall be permitted, provided all of the following conditions are
met:
1. Portable fire extinguishers with a minimum of a 2A: 10B :C
rating are placed at each activity or viewing station;
2. A smoke detection system is placed throughout the facility
with a detector located at each activity or viewing station and located
throughout corridors and halls not to exceed a spacing more than 15 feet (4.6
m) from a wall or more than 30 feet (9.1 m) on center;
3. Emergency lighting shall be provided which will cause
illumination of the means of egress upon activation of the fire alarm, any
required smoke detector, or upon loss of power;
4. Personnel dedicated for the sole purpose of providing a
fire watch shall be stationed at each activity or viewing station. Such
personnel shall be provided with a direct communication device for
communication with all other stations throughout the facility. In addition such
personnel shall be provided with appropriate training for the operation of
portable fire extinguishing equipment;
5. Communication to the responding fire department of
emergency dispatch center is available from the facility;
6. The facility shall be posted prohibiting smoking with
smoking receptacles located a minimum of 15 feet (9.1 m) from the
structure;
7. A fire tour is conducted throughout the structure every
hour and documentation of the time the tour was conducted including the name of
personnel conducting the fire tour is maintained. Such documentation shall be
readily available to the code official upon request."
|
|
(j) |
Modifications
to Chapter 10:
1. |
Delete sections 1001
through 1027 in their entirety and substitute in their place the following:
"1001.1 General. Proposed (new) and
existing buildings or portions thereof shall be provided with means of egress
and related safeguards as set forth by NFP A 101, Life Safety Code,
as adopted by this Chapter. (Refer to Table 102.10, CODES REFERENCE
GUIDE)"
|
2. |
Add the
following section 1001.2 to read as follows:
"1001.2 Overcrowding and Life Safety Hazard
Prevention. Overcrowding or admittance of any person beyond the approved
capacity of a building or a portion thereof shall not be allowed. It is the
responsibility of the manager and the person in charge of a building,
structure, or portion thereof not to allow an overcrowded condition or any
condition which constitutes a life safety hazard to exist, and to take prompt
action to remedy an overcrowded condition or life safety hazard when evidence
of such a condition is noted, or when advised or ordered by the Fire Code
Official or his/her representative. (Refer to 107.6)"
|
3. |
Delete section 1028.1 in its entirety and
substitute in its place the following:
"1028.1General. The means of egress and related
safeguards for buildings and structures or portions thereof shall be maintained
in accordance with this section and with the provisions of NFPA 101,
Life Safety Code, as adopted by this
Chapter."
|
4. |
Delete section
1028.4 in its entirety and substitute in its place the following:
"1028.4 Exit signs, emergency lighting, and
emergency power systems. Exit signs shall be properly maintained and
shall be operable when a building or structure is occupied. Emergency lighting
and emergency power for exit signs shall be maintained so as to be in a state
of operational readiness at any time a building or structure is occupied.
Emergency generators and power systems shall be tested and maintained as set
forth by 604.3 of this Code."
|
|
(k) |
Modifications to Chapter 11:
1. |
Delete section 1103.5 in its entirety and substitute in its place the
following:
"1103.5Dispensing of flammable and combustible
liquids. No dispensing, transfer or storage of flammable or combustible
liquids shall be permitted inside any building or structure.
"Exceptions:
"1. As provided in Chapter 34 of this Code,
provided the provisions are not less protective than the provisions of
any applicable codes and standards adopted by the Rules and Regulations of the
Safety Fire Commissioner.
"2. When the procedures used follow the guidelines and
requirements set forth in NFPA 410 - Standard for Aircraft Maintenance,
adopted by this Chapter."
|
2. |
Delete sections 1106.1 through 1106.21.1
in their entirety and substitute in their place a new paragraph 1106.1 to read
as follows:
"1106.1 Aircraft motor vehicle fuel-dispensing
stations and Airport Fuel Systems. All aircraft motor vehicle
fuel-dispensing stations and airport fuel systems shall be in accordance with
Chapter 120-3-11 Rules and Regulations of the Safety Fire Commissioner
entitled, 'Rules and Regulations for Flammable and Combustible
Liquids'."
|
3. |
Delete
section 1107.1 in its entirety and substitute in its place the following:
"1107.1 General. Helistops and heliports shall
be maintained in accordance with Section 1107. Helistops and heliports on
buildings or structures shall be constructed in accordance with the IBC
and the requirements set forth by NFPA 418, Standard for
Heliports, adopted by this Chapter."
|
|
(l) |
Modification to Chapter 22:
1. |
Delete sections 2201.1 through 2201.6 in
their entirety and substitute in their place a new paragraph 2201.1 to read as
follows:
"2201.1 Scope. Automotive motor
fuel-dispensing facilities, marine motor fuel-dispensing facilities, fleet
vehicle motor fuel-dispensing facilities and repair garages shall be in
accordance with Chapter 120-3-11 Rules and Regulations of the Safety Fire
Commissioner entitled, 'Rules and Regulations for Flammable and Combustible
Liquids'."
Exception: This chapter shall apply to hydrogen
motor fuel-dispensing and generation facilities as specified in section 2209
and repair garages where referenced by subsection 406.6, entitled, 'Repair
Garages,' of the International Building Code.
|
2. |
Delete sections
2203 through 2208 and all other paragraphs there under and section 2210 all
other paragraphs there under in their entirety without
substitution. |
|
(m) |
Modification to Chapter 27:
1. |
Add two new exceptions 11 and 12 to section 2701.1 to read as follows:
"11. Storage, transportation, use, dispensing, mixing
and handling of Flammable and Combustible Liquids as outlined in Chapter
120-3-11 Rules and Regulations of the Safety Fire Commissioner entitled, 'Rules
and Regulations for Flammable and Combustible Liquids.'
12. Storage, handling, and transportation of liquefied
petroleum gas (LP-Gas) and the installation of LP-gas equipment pertinent to
systems for such use as outlined Chapter 120-3-16 Rules and Regulations of the
Safety Fire Commissioner entitled, 'Rules and Regulations for Liquefied
Petroleum Gases'."
|
2. |
In
Table 2703.11.1, add superscript "k"to Oxidizers in the Material column and add
the following footnote "k"to read as follows:
"k. Group M occupancies with Class 2 and Class 3
oxidizers exceeding these quantities shall include fire protection in
accordance with section 7.4 of NFPA 430, Code for theStorage of Liquid and Solid Oxidizers adopted by this
Chapter."
|
|
(n) |
Modifications to Chapter 33:
1. |
Delete sections 3301 through 3307 and all
related paragraphs there under in their entirety and substitute in their place
the following:
"3301. Explosives and blasting. The
provisions of Chapter 120-3-10 Rules and Regulations of the Safety Fire
Commissioner entitled, 'Rules and Regulations for Explosives and Blasting
Agents' shall govern the possession, manufacture, storage, handling, sale and
use of explosives, explosive materials and small arms
ammunitions."
|
2. |
Delete section 3308.1 in its entirety and substitute in its place the
following:
"3308.1GENERAL PROVISIONS. In addition to the
requirements of this Section for the display of fireworks the provisions of
O.C.G.A. Title 25, Chapter 2, and Chapter 120-3-22, Rules and Regulations of
the Safety Fire Commissioner, shall apply. Where there may be a conflict
between a provision of this Section and a provision of the above referenced law
or regulation, the provision of the above referenced law or regulation shall
apply. Nothing in this chapter shall be construed to prohibit the use of
fireworks by railroads or other transportation agencies for the signal purposes
or illumination, or the sale or use of blank cartridges for a show or theater,
or for signal or ceremonial purposes in athletics or sports or for the use by
military organizations."
|
3. |
Delete section 3308.11 in its entirety and substitute in its place the
following:
"3308.11Retail display and sale. (a) Fireworks
as define d in the Official Code of Georgia (O.C.G.A.) Title 25, Chapter 10 in
25-10-1 (a)(1) shall not be made available for sale at retail or wholesale,
except as provided in O.C.G.A.
25-10. (b) Non-explosive sparkling
devices as define d in O.C.G.A.
25-10-1(b)are
permitted for retail sales to the public, provided, however, it is unlawful for
any such devices to be sold to any person under 18 years of age (O.C.G.A.
25-10-2(b)(1). In
addition, it is unlawful to sell such items to any person by any means other
than an in-person, face-to-face sale. Further, such person shall provide proper
identification to the seller at the time of such purchase. The term 'proper
identification' means any document issued by a governmental agency containing a
description of the person, such person's photograph, or both, and giving such
person's date of birth and includes without being limited to, a passport,
military identification card, driver's license, or an identification card
authorized under O.C.G.A. Sections
40-5-100 through
40-5-104. (c) In areas where
devices are stored or displayed for retail sales, at least one
pressurized-water type portable fire extinguisher complying with NFPA 10, as
adopted by this Chapter shall be located not more than 20 feet and not closer
than 15 feet from the storage or display location. In addition, "NO
SMOKING"signs complying with Section 310 shall be conspicuously posted in areas
of such storage or display, unless in a building where smoking is clearly
marked as prohibited."
|
|
(o) |
Modification to Chapter 34:
1. |
Add a new nonapplicability paragraph
number 10 to section 3401.2 to read as follows:
"10. The storage, transportation, use, dispensing,
mixing and handling of Flammable and Combustible Liquids as outlined in Chapter
120-3-11 Rules and Regulations of the Safety Fire Commissioner entitled, 'Rules
and Regulations for Flammable and Combustible Liquids'."
|
|
(p) |
Modifications
to Chapter 38:
1. |
Delete Chapter 38 in
its entirety and substitute in its place the following:
"CHAPTER 38 LIQUEFIED PETROLEUM GASES.The
provisions relating to the storage and handling of liquefied petroleum gases
shall be those in NFPA 58, LiquefiedPetroleum Gas
Code, as adopted by Chapter 120-3-16, Rules and Regulations of the
Safety Fire Commissioner. (Refer to Table 102.10), CODES REFERENCE
GUIDE)"
|
|
(q) |
Modifications to Chapter 45:
1. |
Delete Chapter 45 in its entirety and substitute in its place the following:
"CHAPTER 45 REFERENCED STANDARDS. Replace the
ICC EC - 06 ICC Electrical Code reference with the
Georgia State Minimum Standard Electrical Code
(National Electrical Code). The following are the section
numbers where such references exist:
603.1.3, 603.1.7, 603.5.2, 604.2.16.1, 604.2.16.2, 605.1,
605.3, 605.4, 605.9, 606.16, 904.3.1, 907.6, 909.11, 909.12.1, 909.16.3,
1106.3.4, 1204.2.3, Table 1304.1, 1404.7, 1503.2.1, 1503.2.1.1, 1503.2.1.4,
1503.2.5, 1504.6.1.2.2, 1504.9.4, 1604.5, 1703.2.1, 1803.7.1, 1803.7.2,
1803.7.3, 1903.4, 2004.1, 2201.5, 2205.4, 2208.8.1.2.4, 2209.2.3, 2211.3.1,
2211.8.1.2.4, 2403.12.6.1, 2404.15.7, 2606.4, 2703.7.3, 2703.8.7.1, 2703.9.4,
2704.7, 2705.1.5, 3003.7.6, 3003.8, 3003.16.11, 3003.16.14, 3203.7, 3203.7.2,
3403.1, Table 3403.1.1, 3403.1.3, 3404.2.8.12, 3404.2.8.17, 3406.2.8, 3503.1.5,
3503.1.5.1, 3606.5.5, 3606.5.6, 3704.2.2.8
Replace the NFPA Standard Reference numbers with the year
edition with the same NFPA Standard Reference numbers and titles however; each
year edition shall be those as adopted by the Rules and Regulations of the
Georgia Safety Fire Commissioner Chapters 102-3-3, 120-3-10, 120-3-11 and
120-3-12. The following are the Standard Reference numbers and the section
numbers where such references exist:
NFPA National Fire Protection Association;
Batterymarch Park; Quincy, MA
02269
Standard Referenced reference in code
By number and title section number
________________________________________________________________________
__________________________________
10 Portable Fire Extinguishers ....... .............. Table
901.6.1, 906.2, 906.3,
Table 906.3(1), Table 906.3(2), 2106.3
11 Low-, Medium-, High-expansion Foam . . .................
904.7, 3404.2.9.1.2
11A Medium- and High-expansion Foam Systems . . .......... .
904.7, 3404.2.9.1.2
12 Carbon Dioxide Extinguishing Systems . . . ....... Table
901.6.1, 904.8, 904.11
12A Halon 1301 Fire Extinguishing Systems .................
Table 901.6.1, 904.9
13 Installation of Sprinkler Systems . . . ........ Table
704.1, 903.3.1.1, 903.3.2, 903.3.5.1.1, 903.3.5.2, 904.11, 905.3.4, 907.9,
2301.1, 2304.2, Table 2306.2, 2306.9, 2307.2, 2307.2.1, 2308.2.2, 2308.2.2.1,
2310.1, 2501.1, 2804.1, 2806.5.7, 3404.3.3.9, Table 3404.3.6.3(7),
3404.3.7.5.1, 3404.3.8.4
13D Installation of Sprinkler Systems in One- and Two-family
Dwellings and Manufactured Homes ............................... 903.3.1.3,
903.3.5.1.1
13R Installation of Sprinkler Systems in Residential
Occupancies up to and Including Four Stories in Height . . . . . 903.3.1.2,
903.3.5.1.1, 903.3.5.1.2, 903.4
14 Installation of Standpipe and Hose Systems ..... 905.2,
905.3.4, 905.4.2, 905.8
15 Water Spray Fixed Systems for Fire Protection
................ 3404.2.9.1.3
16 Installation of Foam-water Sprinkler and Foam-water Spray
Systems .................................. 904.7, 904.11
17 Dry Chemical Extinguishing Systems ........... Table
901.6.1, 904.6, 904.11
17A Wet Chemical Extinguishing Systems ........... Table
901.6.1, 904.5, 904.11
20 Installation of Stationary Pumps for Fire Protection . . .
. . 913.1, 913.2, 913.5.1
22 Water Tanks for Private Fire Protection
........................... 508.2.2
24 Installation of Private Fire Service Mains and their
Appurtenances .................................... 508.2.1, 909.5
25 Inspection, Testing and Maintenance of Water-based Fire
Protection Systems .................... 508.5.3, Table 901.6.1, 904.7.1, 912.6,
913.5,
30 Flammable and Combustible Liquids Code . . . 403.6.2,
3403.6.2.1, 3404.2.7, 3404.2.7.1, 3404.2.7.2, 3404.2.7.3.6, 3404.2.7.4,
3404.2.7.6, 3404.2.7.7, 3404.2.7.8, 3404.2.7.9, 3404.2.9.2, 3404.2.9.3,
3404.2.9.5.1.1, 3404.2.9.5.1.2, 3404.2.9.5.1.3, 3404.2.9.5.1.4, 3404.2.9.5.1.5,
3404.2.9.5.2, 3404.2.9.6.4, 3404.2.10.2, 3404.2.11.4, 3404.2.11.5.2,
3404.2.12.1, 3404.3.1, 3404.3.6, 3404.3.7.2.3,3404.3.7.5.1, 3404.3.8.4,
3406.8.3
30A Code for Motor Fuel-dispensing Facilities and Repair
Garages ............... . 2201.4, 2201. 5, 2201.6, 2206.6.3, 2210.1
30B Manufacture and Storage of Aerosol Products
.................. 2801.1,
2803.1, 2804.1, Table 2804.3.1, Table 2804.3.2, Table
2804.3.2.2, 2804.4.1, 2804.5.2, 2804.6, Table 2806.2, 2806.2.3, 2806.3.2, Table
2806.4, 2806.5.1, 2806.5.6, 2807.1
31 Installation of Oil-burning Equipment . . .............
603.1.7, 603.3.1, 603.3.3
32 Dry Cleaning Plants ....................................
1207.1, 1207.3
33 Spray Application Using Flammable or Combustible Materials
....... 1504.3.2
34 Dipping and Coating Processes Using Flammable or
Combustible Liquids ........................... 1505.3, 1505.4.1.1
35 Manufacture of Organic Coatings ..........................
2001.3, 2005.4
40 Storage and Handling of Cellulose Nitrate Film
...................... 306.2
51 Design and Installation of Oxygen-fuel Gas Systems for
Welding, Cutting and Allied Processes ................................. 2601.5,
2607.1, 2609.1
51A Acetylene Cylinder Charging Plants
............................... 2608.1
52 Compressed Natural Gas (CNG) Vehicular Fuel System Code .
........ 3001.1
55 Standard for the Storage, Use and Handling of Compressed
Gases and Cryogenic Fluids in Portable and Stationery Containers Cylinders and
Tanks . . . . ....... 2209.2.1, 3201.1, 3501.1, 4001.1
57 Liquefied Natural Gas (LNG) Vehicular Fuel System Code
........... 3001.1
58 Liquefied Petroleum Gas Code . . . . . . . . . 3801.1,
3803.1, 3803.2.1, 3803.2.1.2, 3803.2.1.7, 3803.2.2, 3804.1, 3804.3.1, 3804.4,
3806.2, 3806.3, 3807.2, 3808.1, 3808.2, 3809.11.2, 3811.3
59A Production, Storage and Handling of Liquefied Natural Gas
(LNG) .................................. 3001.1, 3201.1
61 Prevention of Fires and Dust Explosions in Agricultural
and Food Products Facilities ...................... Table 1304.1
69 Explosion Prevention Systems .................. 911.1,
911.3, Table 1304.1
72 National Fire Alarm Code ............ 509.1, Table
901.6.1, 903.4.1, 904.3.5, 907.2, 907.2.1.1, 907.2.10, 907.2.10.4, 907.2.11.2,
907.2.11.3, 907.2.12.2.3, 907.2.12.3, 907.3, 907.5, 907.6, 907.10.2, 907.11,
907.15, 907.17, 907.18, 907.20, 907.20.2, 907.20.5
80 Fire Doors and Fire Windows ..........................
703.2, 1008.1.3.3
85 Boiler and Combustion System Hazards Code . .
.............. Table 1304.1
86 Ovens and Furnaces
........................................... 2101.1
92B Smoke Management Systems in Malls, Atria and Large Spaces
......... 909.8
99 Health Care Facilities ...................................
...... 3006.4
101 Life Safety Code
............................................. .1025.6.2
110 Emergency and Standby Power Systems . . 604.1, 604.3,
604.4, 913.5.2, 913.5.3
111 Stored Electrical Energy Emergency and Standby Power
Systems ...... 604.1, 604.3, 604.4
120 Coal Preparation Plants ............................. . .
. .. .Table 1304.1
160 Flame Effects Before an Audience .....................
.......... 308.3.6
211 Chimneys, Fireplaces, Vents and Solid Fuel-Burning
Appliances ....... 603.2
230 Fire Protection of Storage ........ . 2301.1, 2308.4,
2310.1, 2501.1, 3404.3.3.9
241 Safeguarding Construction, Alteration, and Demolition
Operations . . . . 1401.1
260 Methods of Tests and Classification System for Cigarette
Ignition Resistance of Components of Upholstered Furniture ..........
805.1.1.1, 805.2.1.1, 805.3.1.1
261 Method of Test for Determining Resistance of Mock-Up
Upholstered Furniture Material Assemblies to Ignition by Smoldering Cigarettes
. . ....... 805.2.1.1, 805.3.1.1
265 Method of Fire Tests for Evaluating Room Fire Growth
Contribution of Textile Wall Coverings in Full Height Panels and Walls . . . .
803.5.1, 803.5.1.1, 803.5.1.2
286 Standard Method of Fire Tests for Evaluating
Contribution of Wall and Ceiling Interior Finish to Room Fire Growth ........
803.1, 803.1.2, 803.1.2.1, 803.5.1
303 Fire Protection Standard for Marinas and Boatyards
................ 905.3.7
385 Tank Vehicles for Flammable and Combustible Liquids
.......... 3406.5.4.5, 3406.6, 3406.6.1
407 Aircraft Fuel Servicing
................................... 1106.2, 1106.3
409 Aircraft Hangars .................................. . . .
. 914.8.2, 914.8.5
430 Storage of Liquid and Solid Oxidizers
............................ 4004.1.4
484 Combustible Metals, Metal Powders, and Metal Dusts . . .
...... Table 1304.1
490 Storage of Ammonium
Nitrate.................................3301.1.5
495 Explosive Materials Code.................. 911.1, 911.4,
3301.1.1, 3301.1.5, 3302.1, 3304.2, 3304.6.2, 3304.6.3, 3304.7.1, 3305.1,
3306.1, 3306.5.2.1, 3306.5.2.3, 3307.1, 3307.9, 3307.11, 3307.15
498 Safe Havens and Interchange Lots for Vehicles
Transporting Explosives...................................3301.1.2
505 Powered Industrial Trucks, Including Type Designations,
Areas of Use, Maintenance, and Operation
...................................2703.7.3
654 Prevention of Fire and Dust Explosions from the
Manufacturing, Processing and Handling of Combustible Particulate
Solids......Table 1304.1
655 Prevention of Sulfur Fires and
Explosions.................... Table 1304.1
664 Prevention of Fires and Explosions in Wood Processing and
Woodworking Facilities ................Table 1304.1, 1905.3
701 Methods of Fire Tests for Flame-propagation of Textiles
and Films........................806.2, 807.1, 807.1.2, 807.2, 807.4.2.2,
1703.5
703 Fire Retardant Impregnated Wood and Fire Retardant
Coatings for Building Materials...........................803.4
704 Identification of the Hazards of Materials for Emergency
Response.......... 606.7, 1802.1, 2404.2, 2703.2.2.1, 2703.2.2.2 2703.5,
2703.10.2, 2705.1.10, 2705.2.1.1, 2705.4.4, 3203.4.1, 3404.2.3.2
750 Water Mist Fire Protection
Systems..........................Table 901.6.1
1122 Model
Rocketry............................................. 3301.1.4
1123 Fireworks Display...........3302.1, 3304.2, 3308.1,
3308.2.2, 3308.5, 3308.6
1124 Manufacture, Transportation, Storage, and Retail Sales
of Fireworks and Pyrotechnic Articles...........3302.1, 3304.2, 3305.1, 3305.3,
3305.4, 3305.5
1125 Manufacture of Model Rocket and High Power Rocket
Motors........3301.1.4
1126 Use of Pyrotechnics Before a Proximate
Audience............3304.2, 3305.1, 3308.1, 3308.2.2, 3308.4, 3308.5
1127 High Power
Rocketry......................................... 3301.1.4
2001 Clean Agent Fire Extinguishing Systems............ Table
901.6.1, 904.10"
|
|
|